Home   /   Produits   /   Variateurs de vitesse   /   NZ2000 série contrôle vectoriel sans capteur  
variateur_NZ2000_b

NZ2000 série contrôle vectoriel sans capteur

NZ2000 série compact vectoriel sans capteur- Capacité de surcharge est de 150% (100%) du courant nominal, 3s pour 180% du courant nominal; Il ya dix auxiliaire fréquence sources.It peut mettre en oeuvre un réglage fin de la fréquence auxiliaire et synthèse de fréquence. Deux types de V / F séparation: séparation complète; moitié séparation ...

Caractéristiques techniques

  • Input voltage,V
  • 220
  • 380
  • Power range, кW
  • 0.4 - 3.7
  • 0.4- 450

Technical Specifications of NZ2000 série contrôle vectoriel sans capteur Variateur de fréquence

Item NZ2000

Standard functions

Méthodes de contrôle

V/F(Voltage / Frequency) control

contrôle vectoriel sans capteur (VC)

Maximum frequency

Vector control: 0–320 Hz

V/F control: 0–3200Hz

Carrier frequency

1.0–16.0 kHz

The carrier frequency is automatically adjusted based on the load features.

Input frequency esolution

Valeur de consigne numérique: 0.01 Hz

Valeur de consigne analogique: 0.025% of maximum frequency

Couple de démarrage

G type: 0.5 Hz/150% (VC);

P type: 0.5 Hz/100% (VC)

Speed range

1:100 (VC)

Speed stability accuracy

± 0.2% (VC)

Torque control accuracy

± 20%

Capacité de surcharge

G type: 60s for 150% of the rated current, 3s for 180% of the rated current.

P type: 60s for 120% of the rated current, 3s for 150% of the rated current.

Torque boost

Auto boost

Customized boost 0.1%–30.0%

V/F curve

Line V/F curve

Multi-point V/F curve

N-power V/F curve (1.2-power, 1.4-power, 1.6-power,1.8-power, square)

V/F separation

Two types: complete separation; half separation

Ramp mode

Straight-line ramp

S-curve ramp

Four groups of acceleration/deceleration time with the range of 0.0–6500.0s

DC braking

DC braking frequency: 0.00 Hz to maximum frequency

Braking time: 0.0–100.0s

Braking action current value: 0.0%–100.0%

JOG control

JOG frequency range: 0.00–50.00 Hz

BJOG acceleration/deceleration time: 0.0–6500.0s

Onboard multiple preset speeds

It implements up to 16 speeds via the simple PLC function or combination of terminal states

Onboard PID

It realizes process-controlled closed loop control system easily.

Auto voltage regulation (AVR)

It can keep constant output voltage automatically when the mains voltage changes.

Overvoltage/ Overcurrent stall control

The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/over current.

Torque limit and control

It can limit the torque automatically and prevent frequent over current tripping during the running process.

Power dip ride through

The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time.

Rapid current limit

It helps to avoid frequent over current faults of the AC drive.

High performance

Control of asynchronous motor are implemented through the highperformance current vector control technology.

Timing control

Time range: 0.0–6500.0 minutes

Communication methods

RS485 (MODBUS-RTU)

Protection mode

Motor short-circuit detection at power-on, input/output phase loss protection, over current protection, overvoltage protection, under voltage protection, overheat protection and overload protection.

Input and output

Input terminal

6 digital input terminals, one of which supports up to 100 kHz high-speed pulse input.

2 analog input terminals, one of which only supports 0–10 V voltage input and the other supports 0–10 V voltage input or 4–20 mA current input.

Frequency source

Digital setting, analog voltage setting, analog current setting, pulse setting and serial communication port setting.

Auxiliary frequency source

There are ten auxiliary frequency sources.It can implement fine tuning of auxiliary frequency and frequency synthesis.

Running command source

You can perform switchover between these sources in various ways.

Output terminal

1 digital output terminal

1 relay output terminal

1 analog output terminal :that supports 0–20 mA current output or 0–10 V voltage output

operation on the operation panel

LED display

It displays the parameters.

Key locking and function selection

It can lock the keys partially or completely and define the function range of some keys so as to prevent mis-function.

Environment

Installation location

Indoor, free from direct sunlight, dust, corrosive gas,combustible gas, oil smoke, vapour, drip or salt.

Altitude

Lower than 1000 m

Ambient temperature

-10°C ~40°C (de-rated if the ambient temperature is between 40°C and 50°C)

Humidity

Less than 95%RH, without condensing

Vibration

Less than 5.9 m/s2 (0.6 g)

Storage temperature

-20°C~60°C